15-96 KWh Low-Voltage Outdoor Battery Cabinet

15-96 KWh Low-Voltage Outdoor Battery Cabinet

Product:low-voltage lithium battery outdoor cabinet
Reference energy range: 15–96kWh
Internal battery pack options: 48V or 51.2V rack-mounted LFP battery packs
Battery pack energy range: 4.8–16.1kWh per pack
Standard and maximum continuous pack rate: 0.5C
Outdoor cabinet protection: Up to IP54
Electrical protections: Overcurrent / overvoltage / short-circuit / lightning protection, as configured
Reference weight: 124–229kg, depending on platform
Deployment: Independent outdoor installation with modular capacity expansion
Send Inquiry
Description
Technical Parameters
LOW-VOLTAGE LITHIUM BATTERY OUTDOOR CABINET
15–96 kWh
CABINET ENERGY RANGE
9 platforms
CABINET OPTIONS
IP54
OUTDOOR CABINET
0.5C
PACK RATE

Product Overview

The modular low-voltage lithium battery outdoor cabinet platform combining 48V or 51.2V rack battery packs with weather-resistant enclosures. Nine cabinet configurations cover reference energies from 15 to 96kWh for outdoor solar storage, backup power and distributed energy projects.

product-933-984

Engineering Features

  • Outdoor Environmental Protection

The enclosure is designed for rain, dust, sunlight and corrosion exposure, with cabinet protection stated up to IP54.

  • Multiple Electrical Protections

The platform description includes overcurrent, overvoltage, short-circuit and lightning protection functions.

  • Modular Capacity Architecture

Independent battery units can be combined into nine reference cabinet platforms for installation, maintenance and later upgrade planning.

  • 48V and 51.2V Pack Options

Six rack-battery configurations cover 4.8–16.1kWh per pack at a standard and maximum continuous rate of 0.5C.

  • Compact Deployment

Three cabinet height classes and two footprint families support different energy and site-space requirements.

Complete Technical Specifications

Lithium Battery Pack Specifications
Parameter
GBP48-100R
GBP48-200R
GBP48-314R
GBP51.2-100R
GBP51.2-200R
GBP51.2-314R
Cell capacity (Ah)
100
200
314
100
200
314
Nominal energy (kWh)
4.8
9.6
15.1
5.12
10.24
16.1
Nominal capacity (Ah)
100
200
314
100
200
314
Nominal voltage (VDC)
48
48
48
51.2
51.2
51.2
Operating voltage range (VDC)
42–54.75
42–54.75
42–54.75
44.8–58.4
44.8–58.4
44.8–58.4
Dimensions (D×W×H, mm)
689×495×162
682×510×246
904×465×252
689×495×162
682×510×246
904×465×252
Reference weight (kg)
46
93
136
49
96
140
Shared Battery Pack Parameters
Standard charge/discharge rate
0.5C
Maximum continuous charge/discharge rate
0.5C
Allowable humidity
85% RH
Storage temperature
−20 to 55°C; recommended 10 to 35°C
Charging temperature
0 to 55°C
Battery pack protection level
IP20
Outdoor Cabinet Capacity Platforms
Model
Dimensions (D×W×H, mm)
Reference weight (kg)
Reference energy (kWh)
BOC-5K-3
1016×715×1000
124
15
BOC-5K-6
1016×715×1500
158
30
BOC-5K-10
1016×715×2200
205
50
BOC-10K-2
1016×715×1000
124
20
BOC-10K-4
1016×715×1500
158
40
BOC-10K-6
1016×715×2200
205
60
BOC-15K-2
1226×715×1000
142
32
BOC-15K-4
1226×715×1500
180
64
BOC-15K-6
1226×715×2200
229
96

All values are reference data and may change without prior notice. Confirm cabinet composition, installed pack quantity, protection design and final dimensions in the approved project datasheet.

Outdoor Enclosure and Protection Basics

IP54 applies to the cabinet boundary

The internal packs are listed as IP20. Open doors, damaged seals or unsealed cable entries can expose those components to the outdoor environment and reduce system protection.

Lightning protection needs an external discharge path

A surge protective device must be coordinated with site earthing, bonding, cable routing and upstream protection. The cabinet alone cannot safely absorb unlimited lightning energy.

Solar exposure changes thermal conditions

Outdoor air temperature is not the only heat source. Direct sun and internal losses can raise enclosure temperature, so orientation, shading and ventilation must be considered.

Reference energy is a configuration value

Confirm installed pack count, nominal and usable energy, DOD limits and inverter compatibility for the actual project-not only the cabinet model name.

Outdoor Battery Cabinet Assembly and Delivery Checks

product-1000-688

Cabinet configuration: Reconcile battery quantity, voltage platform, cabinet options and external interfaces with the approved order.

Outdoor build details: Inspect door alignment, seals, cable entries, ventilation or cooling paths and handling condition before shipment.

Pre-installation release: Record the required electrical, BMS and protection checks so the receiving team has a clear installation baseline.

Selection Guidance

Choose Reference Energy

Select 15–96kWh from load profile and runtime, then verify usable energy, reserve and future expansion.

Match 48V or 51.2V

Confirm the inverter voltage window, charge setpoint, communication protocol and approved pack type.

Check Site Envelope

Verify foundation, clearance, solar exposure, drainage, corrosion category and cable-entry direction.

Define Protection Coordination

Review branch fusing, isolation, surge protection, grounding and upstream fault levels as one system.

Packing and Transport

Ship each battery in approved protective packaging with terminals insulated against short circuit. Confirm required lithium-battery test summaries, labels, documents, state-of-charge limits and carrier restrictions for the selected transport route. Keep packages upright and dry, protect them from impact, and quarantine any unit showing deformation, leakage, unusual odor or abnormal heat.

FAQ

Does an IP54 cabinet make each internal battery pack IP54?

No. The listed packs are IP20. Outdoor protection depends on the complete closed cabinet, intact seals and properly sealed cable entries.

Is reference cabinet energy the same as usable energy?

Not necessarily. Usable energy depends on the installed pack configuration, allowed DOD, operating limits, temperature and system losses.

Can the cabinet be placed directly on soil?

Use an engineered level foundation with drainage, anchoring and cable access appropriate to the cabinet weight and local site conditions.

What information is needed for selection?

Provide load power and duration, inverter model, voltage platform, target energy, environment, foundation, expansion plan and local protection requirements.

modular-1
Configure an Outdoor Battery Cabinet

Send the load profile, inverter model, required energy, voltage platform, site environment, foundation and expansion plan for engineering review.

Hot Tags: 15-96 kwh low-voltage outdoor battery cabinet, China 15-96 kwh low-voltage outdoor battery cabinet manufacturers, suppliers, factory, ac dc ev charging, ac fast charging ev, charger ac to dc

Technical Specifications

Lithium Battery Pack Specifications
Parameter
GBP48-100R
GBP48-200R
GBP48-314R
GBP51.2-100R
GBP51.2-200R
GBP51.2-314R
Cell capacity (Ah)
100
200
314
100
200
314
Nominal energy (kWh)
4.8
9.6
15.1
5.12
10.24
16.1
Nominal capacity (Ah)
100
200
314
100
200
314
Nominal voltage (VDC)
48
48
48
51.2
51.2
51.2
Operating voltage range (VDC)
42–54.75
42–54.75
42–54.75
44.8–58.4
44.8–58.4
44.8–58.4
Dimensions (D×W×H, mm)
689×495×162
682×510×246
904×465×252
689×495×162
682×510×246
904×465×252
Reference weight (kg)
46
93
136
49
96
140
Shared Battery Pack Parameters
Standard charge/discharge rate
0.5C
Maximum continuous charge/discharge rate
0.5C
Allowable humidity
85% RH
Storage temperature
−20 to 55°C; recommended 10 to 35°C
Charging temperature
0 to 55°C
Battery pack protection level
IP20
Outdoor Cabinet Capacity Platforms
Model
Dimensions (D×W×H, mm)
Reference weight (kg)
Reference energy (kWh)
BOC-5K-3
1016×715×1000
124
15
BOC-5K-6
1016×715×1500
158
30
BOC-5K-10
1016×715×2200
205
50
BOC-10K-2
1016×715×1000
124
20
BOC-10K-4
1016×715×1500
158
40
BOC-10K-6
1016×715×2200
205
60
BOC-15K-2
1226×715×1000
142
32
BOC-15K-4
1226×715×1500
180
64
BOC-15K-6
1226×715×2200
229
96

All values are reference data and may change without prior notice. Confirm cabinet composition, installed pack quantity, protection design and final dimensions in the approved project datasheet.

Send Message